A fire alarm must be tested regularly to be trusted. BS 5839-1 recommends a weekly user test (operating a different call point each week so the panel and sounders are checked) and servicing by a competent person at intervals of no more than six months, with results written in a logbook.
Key takeaways
- Weekly: test a call point (rotate through them).
- Every 6 months (max): service by a competent person.
- Batteries age: test and replace as needed.
- Record everything in a logbook.
- Fix faults promptly: a system in fault may not alarm.
01The schedule
| When | What | Who |
|---|---|---|
| Weekly | Operate one manual call point; check sounders and panel reset | Trained staff |
| Every 6 months (maximum) | Service: panel, batteries, devices, cause-and-effect | Competent technician |
| Across the year | Every detector and call point tested | Competent technician |
| After any alarm or fault | Record, investigate, fix | Staff + technician |
02What a proper service covers
- Panel functions and fault indications
- Standby battery condition and charger
- Detectors tested with the correct test equipment
- Call points operated
- Sounders and beacons checked
- Cause-and-effect confirmed
- Logbook updated

03Warning signs
- Panel showing a fault light
- Repeated false alarms
- Beeping from the panel (often batteries)
- Detectors painted over or covered
04Frequently asked questions
How often should a fire alarm be serviced?
BS 5839-1 recommends at least every six months by a competent person, plus weekly user tests.
Why test a different call point each week?
So that over time every call point is proven to work.
Why is my fire alarm panel beeping?
Usually a fault: often a battery, a disconnected device or a wiring fault. Have it checked.