DC Cable Voltage Drop Calculator

Check that your cable is thick enough so cameras, locks and gate motors get the voltage they need.

By Qyvea LimitedUpdated 2026-10-17
Enter your numbers above.

How it is calculated

Voltage drop = 2 x length x current x 0.0175 / cross-section (mm2) for copper, where 0.0175 is copper resistivity in ohm mm2 per metre and the factor 2 counts the go and return conductors. Keep drop under 5% (3% for sensitive loads). Use pure copper cable, not copper-clad aluminium.

Results are estimates for planning. Real systems depend on site conditions; Qyvea surveys and quotes before installation.

Tips from our installers

  • Low-voltage runs lose far more than mains runs: doubling the length doubles the drop.
  • For long runs, power the device locally or use a higher voltage.
  • Gate motors and locks draw peak current when they start: size for the peak.

Frequently asked questions

What drop is acceptable?

About 5% or less is a common guideline for low-voltage loads.

Why do cheap cables fail?

Many are copper-clad aluminium, which has higher resistance than the label suggests.

Does this apply to AC mains?

The same formula applies with different limits; use proper electrical design for mains.